1,300+ pages, 20 chapters
The clause you need sits somewhere between emergency lighting in Chapter 6 and smart monitoring in Chapter 16. Scrolling a PDF on a site walk is not a workflow.
The UAE Fire & Life Safety Code is 20 chapters and 1,300+ pages. SparkProof reads it for you: ask in plain English or Arabic and get the answer with the chapter cited — before the DCD inspector asks.
Free plan included · No card required · English + العربية
You
Can I use a conventional fire alarm panel in a new building?
SparkProof
No. Chapter 8 permits only listed and approved addressable fire detection and alarm systems in new construction — conventional systems are acceptable only where they already exist. Every building must have an automatic addressable fire detection and alarm system.
Source: UAE Fire & Life Safety Code 2018 · Chapter 8
The clause you need sits somewhere between emergency lighting in Chapter 6 and smart monitoring in Chapter 16. Scrolling a PDF on a site walk is not a workflow.
Products need Civil Defence listing — overseas certificates alone do not qualify. A conventional panel or an unlisted cable can fail the final inspection after it is already installed.
Chapter 18: nobody occupies the building before final commissioning and clearance. Every missing test report or certificate delays the opening — and your payment.
Real questions from site, answered with the exact requirement and the chapter behind it.
Travel distance to the nearest manual call point must not exceed 61 m — reduced to 25 m or 16 m in limited-mobility areas or where rapid fire development is likely. Mount at about 1.2 m above floor level, within 1.5 m of exit door openings, and the alarm signal must follow within 10 seconds.
Source: UAE Fire & Life Safety Code 2018 · Chapter 8
Type 10 / Class 3: the emergency supply must cut in within 10 seconds of mains failure and the batteries must last 3 hours (180 minutes), with at least 1.1 lux at floor level along the egress path. Maintenance is codified too — a 30-second mains-failure test every month and a full 3-hour discharge test annually.
Source: UAE Fire & Life Safety Code 2018 · Chapter 6
Circuits that must keep working during a fire need fire-rated cable certified for 120 minutes to EN 50200, UL 2196, BS 8434-2, BS 7629-1 or BS 6387 — plus Civil Defence listing. Ordinary “flame retardant” cable does not qualify.
Source: UAE Fire & Life Safety Code 2018
The DCD inspection points — alarm placement, emergency lighting tests, 120-minute cable certificates, smart monitoring link — condensed to one page. Get it by email.
Create a free account and ask your first Fire Code question — the cited answer arrives in seconds, in English or Arabic.